My first solar and battery backup system
#1
Hi everyone.

This is my first build and I am currently working on the design.  I will welcome any input and recommendations on my design.  I have included a basic outline of my plan below.  I am not able to get exact power usage information on the 120VAC side because I am currently out of country on business.  I am estimating that my max wattage needed at any given time will not exceed 10kW, but I will confirm when I return home (Southern Mississippi, Gulf Coast, USA).



I can't afford the cost to go completely off the grid, but my house has 2 breaker panels already.  One is the 240VAC (H-N-H) Main Service with the meter, has breakers for all the 240 loads, and has a breaker that provides power to the 120VAC Aux breaker.  The AUX breaker is where all my 120VAC gets distributed to the various circuits in the house.  What I am planning to do is disconnect the 120VAC line from the Main Service and run it to my solar and powerwall build.

I want to use 4 x 48VDC battery packs (18650 14S28P) in parallel to provide just over 10kWh of power.  (This will be increased as time/funds allow).
I am planning on using 2 x 12AWG copper wire twisted together for my bus bar.  24 AWG copper wire to connect the cells on the non-fused side (bottom) of the battery packs, and 34 AWG copper wire to make the fuses (top).

I want to use 8 x 340W solar panels to generate the energy.  My roof only has one South facing side with enough room to accommodate 8 panels.  At my location I can count on 4.5 Sun Hours averaged daily.

Where I need help:
Am I using acceptable wire gauge for my battery packs?
Does anyone have recommendations for battery chargers/inverters for my planned design?
Have I forgotten or missed something that I need to know before I start?

Thank you all in advance!!!
Lawcomleo and Korishan like this post
Reply


#2
Welcome to the Powerwallers! Cool

I see you've done your research before posting and asking questions. Kudos! :thumbs-up emoji:

In Fl, the main breaker box (metered; outside residence building) is really only intended for outside and heavy load use (central unit, separate building, etc). Even though it's a 240 panel, it has twin 120 rails. Same goes for your panel that is on the inside (usually in kitchen or garage) of the house. It has twin 120 rails and you use a 240 setup to get power to your heavy inside loads like the dryer, oven, etc.
So both panels should be rated for 240V max. Now, the inside panel may only be 200A, or less. The metered panel would be like 300 or 400A. The reason the sub-Panel would be 240V capable as well is to have balanced loads on each hot leg.
That was more for a clarification, more than anything else. Codes in Miss may be different on this, I dunno.

That's a good startup. 48VDC would give you minimal voltage loss and plenty of amps when needed (by the inverter). I'm going to assume you are going to build the packs with Serial and Parallel runs, then connect the packs in Parallel with each other. Are you going to do Parallel-Serial or Serial-Parallel in each pack (just curious about this configuration). Parallel-Serial is you have 14 single cells in series, then you hook each string in Parallel, then the packs in Parallel. Parallel-Serial is you have x-number of cells connected in Parallel, then those are in strings of 14 parallels, then the packs in parallel.

2 x 12 awg cables twisted is good. Just make sure they are tight. Several videos by AveRageJoe shows this process. There are others as well.
Getting a 48V inverter in the US is kinda hard. Well, sorta. Depends on what you're looking for. If you are wanting a Grid-Tie, then that's hard to find. If it's just a stand alone unit, then that's pretty easy. If you're wanting the Inverter to also charge, that makes it a little more difficult. I'm personally going to have two separate units for charging and for inverting for the bulk. As a backup source for charging, I'll be using some repurposed UPS's.

What are the voltages for the panels? Open and loaded voltages; rated amps; manufacturer; poly or mono-crystallines?

Again, welcome Smile
Proceed with caution. Knowledge is Power! Literally! Cool 
Knowledge is Power; Absolute Knowledge is Absolutely Shocking!
Dollar Shave Club. Best Razor I've ever used
Certified 18650 Cell Reclamation Technician
Reply
#3
Korishan,
Thank you for the feedback.
The 120VAC AUX panel was replaced earlier this year by an electrician friend of mine when i gutted and renovated my house, so I will check with him to verify (Thanks for catching that).
The plan for the battery packs is 14S28P, but I want to build a Proof of Concept pack first. I will use a vice clamp and drill to twist the two 12AWG wires together. I have seen a few videos of that working well.
This system will be completely isolated from the grid, so I'm looking at possibly using Aims inverter/charger (PICOGLF10KW48V240VS) which is rated at 10kW (30kW surge) and is 48VDC and will do 120/240VAC. Priced it online new at $2350.00 USD, Which looks like a good deal to me.
I haven't decided on the PV panels yet. I know I need 8x 340W panels and will go with the monocrystalin, but I haven't got much further than that.
Reply
#4
(08-02-2017, 01:31 PM)Robert Crawley Wrote: Korishan,
Thank you for the feedback.  
The 120VAC AUX panel was replaced earlier this year by an electrician friend of mine when i gutted and renovated my house, so I will check with him to verify (Thanks for catching that).  
The plan for the battery packs is 14S28P, but I want to build a Proof of Concept pack first.  I will use a vice clamp and drill to twist the two 12AWG wires together.  I have seen a few videos of that working well.
This system will be completely isolated from the grid, so I'm looking at possibly using Aims inverter/charger (PICOGLF10KW48V240VS) which is rated at 10kW (30kW surge) and is 48VDC and will do 120/240VAC. Priced it online new at $2350.00 USD, Which looks like a good deal to me.
I haven't decided on the PV panels yet.  I know I need 8x  340W panels and will go with the monocrystalin, but I haven't got much further than that.

I don't have any experience with AIMS products, but if you're going to spend $2300, why not buy a proper inverter like a Magnum that's UL-listed, parallelable, split phase, etc?
Korishan likes this post
Solar Setup: 9x 320w panels, PCM60X charge controller
Battery Setup: 14x 120 cell 18650 packs, 48v configuration

Recommended Items:
Opus BT-C3100, Cell Heat Shrink, 4-Cell Holders
Reply
#5
I didn't think about it when I decided to use the UPS's for my inverters/chargers/gridtie(ish) setup. But, using those, they are at least UL listed and rated for the US power grid. So, I guess going that route, I'm in good company. Though, I wonder if the UL listing carries over when you alter the device Tongue
Proceed with caution. Knowledge is Power! Literally! Cool 
Knowledge is Power; Absolute Knowledge is Absolutely Shocking!
Dollar Shave Club. Best Razor I've ever used
Certified 18650 Cell Reclamation Technician
Reply
#6
(08-02-2017, 01:46 PM)Korishan Wrote: I didn't think about it when I decided to use the UPS's for my inverters/chargers/gridtie(ish) setup. But, using those, they are at least UL listed and rated for the US power grid. So, I guess going that route, I'm in good company. Though, I wonder if the UL listing carries over when you alter the device  Tongue

I think you voided that as soon as you broke the "warranty void if seal broken" sticker Wink
Korishan likes this post
Solar Setup: 9x 320w panels, PCM60X charge controller
Battery Setup: 14x 120 cell 18650 packs, 48v configuration

Recommended Items:
Opus BT-C3100, Cell Heat Shrink, 4-Cell Holders
Reply
#7
Mike, thank you for the advice. I got too focused on one brand, and you are right. I need something that is UL approved and parallelable for future expansion. I will continue looking for an inverter/charger(s) that will meet my 10kW needs. I'm setting my max price point at $2500 USD, if you have any recommendations.

Korishan, you can buy new anti-tamper stickers online. Just make sure you completely remove the old one.
Reply
#8
(08-02-2017, 02:40 PM)Robert Crawley Wrote: Mike, thank you for the advice.  I got too focused on one brand, and you are right.  I need something that is UL approved and parallelable for future expansion.  I will continue looking for an inverter/charger(s) that will meet my 10kW needs.  I'm setting my max price point at $2500 USD, if you have any recommendations.  

Korishan, you can buy new anti-tamper stickers online.  Just make sure you completely remove the old one.

You would need 2.5x the Magnums then for 10kw. That's where I'm stuck at and the reason I haven't bought a good inverter yet. There very limited options for the US.

Also, pretty sure that's fraud. Lol Wink
Solar Setup: 9x 320w panels, PCM60X charge controller
Battery Setup: 14x 120 cell 18650 packs, 48v configuration

Recommended Items:
Opus BT-C3100, Cell Heat Shrink, 4-Cell Holders
Reply
#9
The fridge and freezer is the last thing I would start with.
All I'm thinking of is cost of ownership.
When the solar don't work you loose 800 in food.
The water heater would be at the top of my list, They suck tons of power.
Reply
#10
(08-02-2017, 07:50 PM)1958 greyhound Wrote: The fridge and freezer is the last thing I would start with.
All I'm thinking of is cost of ownership.
When the solar don't work you loose 800 in food.
The water heater would be at the top of my list, They suck tons of power.

Grey, 
thanks for you advice.  I will consider putting in a manual switch that would allow me to use grid power if solar and battery fail.  Good Idea.

The 2 refrigerators and freezer are a constant load, and I want to make sure that the food doesn't go bad by having them on this system.

My water heater is an electric tankless on demand water heater that uses 11kW (water heater).  I don't want to put that much load on my system until I can upgrade it to handle 30kW and be able to go off grid completely.

(08-02-2017, 04:32 PM)mike Wrote:
(08-02-2017, 02:40 PM)Robert Crawley Wrote: Mike, thank you for the advice.  I got too focused on one brand, and you are right.  I need something that is UL approved and parallelable for future expansion.  I will continue looking for an inverter/charger(s) that will meet my 10kW needs.  I'm setting my max price point at $2500 USD, if you have any recommendations.  

Korishan, you can buy new anti-tamper stickers online.  Just make sure you completely remove the old one.

You would need 2.5x the Magnums then for 10kw. That's where I'm stuck at and the reason I haven't bought a good inverter yet. There very limited options for the US.

Also, pretty sure that's fraud. Lol Wink

I'm thinking of using a 10kw Solar inverter system MPPT solar charger 80A*2 (PIP 5048MS*2 in parallel).  What do you guys think?  This would allow me to expand my system in the future by adding additional inverters and will let me put my solar panels (I think) into separate strings facing different directions (1060 SqFt. house, small roof).

Please let me know what you guys think and if anyone is using a similar set up.
Bob Smith likes this post
Reply


Who read this thread?
100 User(s) read this thread:
hbpowerwall (09-16-2017, 01:59 AM), AZ_Tekkie (08-08-2017, 03:29 AM), daromer (09-01-2017, 12:22 PM), mike (08-31-2017, 12:50 PM), Toochi84 (08-04-2017, 02:40 PM), BigBen (08-02-2017, 07:35 PM), Andreas Kvernes (08-02-2017, 05:37 PM), owitte (09-01-2017, 03:09 PM), opus40 (08-02-2017, 06:34 AM), miwall (Yesterday, 05:40 AM), VdVoort4 (08-30-2017, 12:29 PM), riveracc1 (08-10-2017, 03:07 AM), coolfx (08-09-2017, 08:50 AM), Herebus (08-08-2017, 04:27 AM), ruby2 (09-01-2017, 06:57 AM), Korishan (09-01-2017, 05:32 PM), PAF (09-01-2017, 12:28 PM), FERCSA (08-09-2017, 04:31 PM), Prahe86 (08-09-2017, 07:08 PM), Wattsup (09-01-2017, 07:45 AM), BobinTN (09-10-2017, 01:33 PM), Tristan Timmer (09-03-2017, 07:50 PM), Frnandu Martiński (08-03-2017, 01:20 PM), egam (08-10-2017, 03:26 AM), CrankyCoder (08-03-2017, 07:32 PM), Alec_J (08-30-2017, 10:40 AM), flight4900 (09-01-2017, 01:17 PM), jdeadman (09-02-2017, 12:32 AM), charlie246 (09-03-2017, 11:08 AM), 2146 (08-03-2017, 08:39 PM), wim (09-01-2017, 02:22 PM), wimpie007 (08-27-2017, 10:03 AM), Joe Farrugia (08-09-2017, 05:10 AM), frnandu (09-02-2017, 09:38 PM), josearaujo10 (08-04-2017, 10:04 PM), typ49 (09-01-2017, 07:14 AM), The-J-Man (08-05-2017, 11:14 AM), annetaesift1959 (08-03-2017, 12:24 AM), Tommy Ng (08-13-2017, 06:21 AM), Charles Francis Speakman (08-06-2017, 12:49 PM), Jeremy Choy (08-08-2017, 07:36 PM), 1958 greyhound (08-10-2017, 08:39 PM), Abarth595 (08-28-2017, 10:12 AM), Quigibo27 (08-03-2017, 03:39 AM), kktuo (08-08-2017, 03:58 PM), watts-on (09-01-2017, 02:46 PM), Dan Lim (08-11-2017, 12:30 AM), jesusangel (09-01-2017, 07:14 PM), fcbrand (09-10-2017, 11:08 PM), volvo09 (08-28-2017, 06:25 PM), Emanuel Huard (08-28-2017, 04:30 PM), Daggerzz (08-29-2017, 06:15 AM), Hanssing (09-01-2017, 03:05 PM), MetalFang (08-03-2017, 08:43 PM), autobd (08-11-2017, 03:15 PM), Bobby (09-03-2017, 01:34 PM), IronSky (09-01-2017, 07:15 AM), silverse2m6 (09-02-2017, 12:10 PM), ismaildoganw (08-03-2017, 07:22 AM), kazbach (08-03-2017, 01:09 AM), Larry Tipton (08-03-2017, 02:56 PM), michael40324 (08-10-2017, 07:23 PM), Davel (08-16-2017, 11:41 AM), Stefaan De Ridder (09-01-2017, 12:55 PM), zimo (08-28-2017, 12:37 PM), Quebec_PW (08-28-2017, 11:23 PM), Chiptosser (08-09-2017, 03:25 AM), rainbowwarrior38 (09-03-2017, 11:00 AM), systemtm (08-04-2017, 06:03 PM), Inverted 18650 (08-08-2017, 03:01 AM), Lawcomleo (09-15-2017, 03:11 PM), BlueSwordM (08-08-2017, 10:41 PM), schujk (08-03-2017, 09:27 PM), Johnny Stauersbøl (08-05-2017, 10:47 PM), Dennis Van Hoek (09-01-2017, 02:21 PM), brafi (08-12-2017, 07:51 AM), pruesel (08-03-2017, 02:14 PM), Stew Mohr (08-08-2017, 10:28 AM), Nitroghost (09-01-2017, 11:15 PM), Erik Smith (09-05-2017, 01:33 AM), N00bPwr (08-12-2017, 06:03 AM), Eric Koshinsky (08-08-2017, 03:52 PM), colishere (08-08-2017, 03:43 AM), John Bender (08-29-2017, 01:19 AM), KaminoReal (08-02-2017, 10:49 AM), David Fairfield (08-08-2017, 08:36 AM), Robert Crawley (09-01-2017, 02:32 PM), KtB (08-28-2017, 06:14 AM), barthy (09-02-2017, 09:53 PM), Pyro (08-02-2017, 08:38 PM), DarthPatrik (08-02-2017, 01:17 PM), stuartornum (08-02-2017, 01:50 PM), Asterix (08-03-2017, 02:38 PM), Jeffrey King (08-04-2017, 01:48 PM), Daveyboy (08-08-2017, 08:31 AM), Licup (08-07-2017, 06:47 PM), suds32 (08-10-2017, 07:45 PM), Seedser (09-01-2017, 02:56 AM), LordGarak (08-10-2017, 04:18 PM), paraskevas (09-07-2017, 11:38 AM)